Information:
Illustration 1 g00687608
The GSC+ uses the run relay (RR) in order to activate the starting aid system. The GSC+ provides a set of contacts of the run relay (RR1) for the customer's use. The RR is located within the relay module. The starting aid switch (SAS) is located on the front panel.The GSC+ activates the RR during engine cranking and running.Note: Whenever the GSC+ activates or the GSC+ attempts to activate the RR, "K5" is shown on the lower display. When the RR is not activated, "K5" is not shown.The possible cause of a CID 0445 FMI 12 is an open coil or a shorted coil of the RR.The system responses to this diagnostic code are listed below.
If a CID 0445 FMI 12 occurs and the RR is activated, the SAS will be disabled. Any customer's equipment on RM-23 of the relay module will be disabled.
If a CID 0445 FMI 12 occurs and the RR is not activated, the SAS will not be enabled. Any customer's equipment on RM-23 of the relay module will not be activated.The GSC+ treats a CID 0445 FMI 12 as an alarm fault. Active alarm faults are shown on the display when the "Alarm Codes" key is pressed. Also, the engine control switch (ECS) must be in any position except the OFF/RESET position. Clear the diagnostic code from the fault log after troubleshooting is complete.This troubleshooting procedure is for an active CID 0445 FMI 12 or the troubleshooting procedure is for an inactive CID 0445 FMI 12.Test Step 1. CHECK THE STATUS OF THE DIAGNOSTIC CODE.
Turn the ECS to the OFF/RESET position and then turn the ECS to the STOP position.
Press the "Alarm Codes" key.
Observe the upper display. Check that the CID 0445 FMI 12 is active.
If the diagnostic code is not active, enter the Service Mode. View the fault log for a OP1. Check that the diagnostic code is inactive.Expected Result:A CID 0445 FMI 12 is displayed as an active diagnostic code or CID 0445 FMI 12 is displayed as an inactive diagnostic code.Results:
OK - The CID 0445 FMI 12 is active or the CID 0445 FMI 12 is inactive. Proceed to test step 2.
NOT OK - The CID 0445 FMI 12 has not occurred. The diagnostic code is not active and the diagnostic code is not inactive. Stop.Test Step 2. CHECK THE INTERNAL CABLE OF THE RELAY MODULE.Note: Only open the relay module in a dry environment. If the relay module is open for more than twenty minutes replace the desiccant bag which is located within the housing of the GSC+. See Testing And Adjusting, "Relay Module - Replace".
Turn the ECS to the OFF/RESET position.
Disconnect the battery negative cable.
Temporarily, remove the relay module from the GSC+. See Testing And Adjusting, "Relay Module - Replace".
Check the cable that attaches the relay module to the GSC+.Expected Result:The cable should be firmly seated in